electric cable equivalents
Standard Wire Gauge to metric

The British Standard Wire Gauge (not to be confused with the Steel Wire Gauge, also with the symbol SWG) is based on the wire's diameter. The metric conductor sizes are based on the nominal area of the cross section of the conductor. The actual cross-sectional areas depend in part upon the stranding of the cable.

A cable with the metric value shown will have at least as much carrying capacity as the SWG cable for which it is being substituted. In other words, values have always been rounded up. For that reason, do not use this table to find the SWG equivalent to a metric cable. For that, go here.

The table assumes the metric-sized cable is substituted for an SWG-sized cable of the same type. It cannot be used, for example, to find a metrically-sized aluminum cable to substitute for a copper SWG cable. If the types are dissimilar, consult the cable manufacturer's literature to determine capacity.

For
Standard Wire Gauge
Substitute Metric
Nominal Cross-sectional Area,
square millimeters
7/0 150
6/0 120
5/0 95
4/0 95
3/0 95
2/0 70
0 70
1 50
2 50
3 35
4 35
5 25
6 25
7 16
8 16
9 16
10 10
11 10
12 6
13 6
14 4
15 4
16 2.5
17 2.5
18 1.5
19 1
20 0.75
21 0.75
22 0.5